Description
CPC EARTH SIZE CALCULATOR
The Adiabatic Equation Calculator is for calculating the absolute minimum permitted circuit protective conductor size, or for verifying an existing protective conductor is adequately sized.
CALCULATING PROTECTIVE CONDUCTOR SIZA
The current edition (at time of writing) of BS 7671 states:
The cross-sectional area of each protective conductor, other than a protective bonding conductor, shall be:
- (i) Calculated in accordance with regulation 543.1.3 or
- (ii) Selected in accordance with regulation 543.1.4
This Adiabatic Equation Calculator App is designed to assist in satisfying option (i) above.
- Calculating the Adiabatic Equation need not be daunting, get the app!
Features
CALCULATES
- Conductor mm²
- la = Fault current
- I² = Fault current²
- k = Conductor k value
- t = Disconnection time
App Reviews
Don’t take our word for it – here’s what other app users say:
Seem to work spot on , comes up with the same answer as i calculate on paper.
Brilliant. So easy and quick to use.
Awesome app so easy to use with correct results.
Brilliant. So easy and quick to use.
Adiabatic Calculator
SIMPLE TO USE
The Adiabatic Equation Calculator couldn’t be any easier to use, just enter your voltage and Zs values, then select your choice from the following drop down options.
Options:
- Protective Device
- Protective Device Rating
- Protective Conductor Type
- Protective Conductor Material
Then tap the “Calculate” button to get the results, it is that simple!
Protective Device
DEVICE TYPE | DEVICE RATING
We have pre-programmed in the operating time / current characteristics for the protective device circuit breakers, fuses and RCBO’s so you don’t need to look them up.
Protective Devices:
- MCB’s
- RCBO’s
- Fuses
Device Ratings:
- Depends on selected protective device
Protective Conductor
TYPE | MATERIAL
Select your choice of protective conductor type, then conductor material. The options available for protective conductor material depends on the selected conductor type.
Types of Protective Conductors:
- Single cable not bunched
- Incorporated in a cable or bunched with cables
- Sheath or armour of cable
- Steel conduit or trunking
Protective Conductor Material:
- Copper
- Aluminium
- Steel
- Lead
Protective Conductor k Values:
Conductor k values have already been set, your protective conductor type and conductor material selections will automatically set the values of k for you.
Adiabatic Calculation
RESULTS
Once you have completed the quick steps mentioned above, tap the calculate button to get the results.
In addition to calculating the protective conductor size the Adiabatic Equation calculator also displays all the other relevant calculation results associated with the final calculation of the earth / earthing conductor / protective conductor size.
Adiabatic Equation Calculation Results
Resulting Parameters:
- Conductor size mm²
- la
- I²
- k
- t
Tablets and Phones
OPTIMISED FOR MULTIPLE SCREEN SIZES
Adiabatic Equation Calculator is optimised to work on all screen sizes and resolutions from the iPhone 5 up to large tablets such as the iPad Pro and all Android devices.
Features:
- Easy to use
- Preset data
- Quick and instant results
- Dedicated support team
DOWNLOAD YOUR ADIABATIC EQUATION APP TODAY!
What is the minimum size of a circuit protective conductor (cpc)
The minimum size of a cpc can be selected from the appropriate table in BS 7671 or it can be calculated using the Adiabatic Equation, the later method will determine the minimum csa size (cross section area) of a cpc required, if the calculated minimum size of protective conductor does not exist, then the next larger size up shall be selected.
Maximum Operating Time Current Characteristic Tables
The maximum operating time current tables cable found in the following tables of BS 7671,
- Fig 3A2 (a,b) – BS 3036 Semi-enclosed Fuse
- Fig 3A3 (a,b) – BS 88-2.2
- Fig 3A4 – BS EN 60898 / 61009-1 MCB/RCBO Type B
- Fig 3A5 – BS EN 60898 / 61009-1 MCB/RCBO Type C
- Fig 3A6 – BS EN 60898 / 61009-1 MCB/RCBO Type D
- BS 1361 Fuse
The relevant fault current time curve values have been pre-set in the Adiabatic Equation App and are automatically applied to the Adiabatic calculation.
For cable limiting temperatures see Protection Against Exceeding Cable Limiting Temperatures
Conductor k Values
Conductor values of k can be found in the following tables of BS 7671,
- Table 54.2 – Conductor not incorporated in a cable and not bunched with cables.
- Table 54.3 – Conductor incorporated in a cable or bunched with cables.
- Table 54.4 – Sheath or armour of a cable.
- Table 54.5 – Steel conduit or trunking
The relevant conductor k values have been pre-set in the Adiabatic Equation App and are automatically applied to the Adiabatic calculation.
Adiabatic Calculation Example
Here we demonstrate an adiabatic equation calculation example, we will explain how the adiabatic equation calculator works.
1. Enter a measured voltage value Uo i.e. 230V.
– The voltage value needs to be a measured value in-order to carry out an accurate calculation, Uo is the voltage to earth.
2. Enter a measured Zs value = 0.26 Ohms.
– The Zs value needs to be a measured value in-order to carry out an accurate calculation, Zs is the earth (fault) loop impedance.
3. Select a protective device type i.e. BS EN 60898 Type B.
4. Select a protective device rating i.e. 10 Amps.
5. Select a conductor type i.e. Single cable not bunched.
6. Select a conductor material i.e Copper – 70°C Thermoplastic.
Adiabatic Calculation Results:
la (PEFC) = 884.62
I² = 782552.54
k = 143
t (s) = 0.1
Conductor csa = 1.956 mm²
As 1.956 mm is not a standard cable size the next available larger cable size shall be used.
la is the prospective earth fault current, I² is the fault current squared, k is the conductor k value, t is the disconnection time in seconds and conductor csa is the cpc earthing conductor size in millimetres.